Cooling·Heating / Air Heat Pump

Air Source Heat Pump


MCHV-P1800A1 (Compact Cube)

• Compact with VFLOW air heat exchanger and DC INVERTER scroll compressor,

High-efficiency cooling and heating (hot water) devices that meet energy saving provide a pleasant environment.


Dual Inverter mount 

COMPAX control


Use Inverter compressor

& Inverter fan


30% reduction of installation area by VFLOW

Apply SIDE FAN.

Protecting equipment even during heavy snow.


MCHV-P1800A1


■ Operating range of air conditioning and heating

■  Compact Cube MCHV Series Features

■ MCHV SERIES Specification table

Classification/Model MCHV-P1800A1
Heating system Air conditioning 
Power
Phase 3 380V 60㎐
PerformancekW160 (137,600 kcal/h)180 (154,000 kcal/h)
Circulation volume
L/mm459.0516.0
Power consumptionkW41.653.7
COP
3.853.35
Appearance dimension
W×L×Hmm1,950×2,060×H2,450
CompressorModel (Maker)HNB78FA (MITSUBISHI ELECTRIC)
Type × Quantity
/ Operation method
Complete sealing scroll  x 4 units  / Inverter operation
Capacity control
100 ~ 40 - 0100 ~ 10 - 0
Rated outputkW12.5 x 4
Legal freeze tone
RT19.90
RefrigerantTypeR410A
Filling amount
(Grid½)
kg36 / 36
Airside heat exchanger type
FIN & COIL TYPE
Waterside heat exchange format
TypePlate 
Inlet/outlet pipe
A65 / 65
BlowerTypePropeller fan
PowerxQuantity kW0.6 × 6
Air volume
(cooling/heating)
m³/min1,128 / 691
ControlDefrostingThe gas discharge reverse method
Water temperature control
Exit temperature control
Driving control
Micom Controller (Fully Automatic driving)
The operating
temperature condition
The temperature outside
: -15 ~ 25
The temperature outside
: -15 ~ 43
Cold and hot outlet temperature
 : 35 ~ 55
Cold and hot outlet temperature
 : 5 ~ 25
Protective device
An overcurrent relay, LPS/HPS, Exhaust gas temperature sensor,

Freeze prevention sensor, Water temperature control at the outlet,  Micom Controller. (Electronic exercise)


NoisedB65 ~ 69
High pressure gas control act
n/a
Weight of the product/operatekg1,780/1,830

※ Standard application temperature:

Heating power: ambient temperature: 7℃, Hot water import port: 40℃, Hot water outlet: 45℃

※ Standard application temperature:

Cooling ability: Outside temperature: 35℃, Coldwater outlet: 12℃, Coldwater outlet: 7℃

※ The specifications and specifications can be changed without prior notice due to product improvement.

※The above picture is a standard product image and may be partially changed depending on the design specifications and option conditions of the site.

Main Use

Swimming pool
Swimming pool
Hot tub
Hot tub
Resort
Resort
Hotel
Hotel
Sports facility
Sports facility