PUHZ-HW140XHA2 (for Cooling/Heating)

• Heat pump systems are attracting attention as a decisive catalyst in energy-saving efforts. Using this technology, heat from the atmosphere is collected. In other words, heat is collected from the atmosphere and used as a heat source that provides high-efficiency cooling and heating.

For example, a heat pump with a coefficient of performance (COP) of 4.0 generates 4 kW of heat output by adding 1 kW of electrical energy input and 3 kW of thermal energy transferred from the outside to the heat pump.


Inverter

compressor

built-in.

Liquid refrigerant → Gas + Liquid conversion energy efficiency           

                 improvement


Increase the volume of circulating refrigerant.

Improving heating capacity in low outdoor air.

Expanding the driving range of flash-in-junction circuits -25℃ cold terrain

R-410A

■ Features 1: Eco-friendly, reducing driving costs.

■ Feature 2: Increase installation and construction convenience

■ Characteristic 3: Excellent heating performance at -25°C

The flash injection circuit is a key component of high heating performance. This technology surpassed the heating capacity by 30% even when operated at sub-zero outdoor temperatures, expanding the operating range to -25°C.

Use it for heating safely even in cold areas.

■ PUHZ SERIES Specification table

 Itme / TypePUHZ-HW140XHA2Remarks/note 
Heating system Air conditioning 
Power
Phase 3 380V 60㎐
PerformancekW14 (12,040 kcal/h)12.5 (10,750 kcal/h)
Circulation volume
L/mm40.135.8
Power ConsumptionkW4.404.82Maximum input current 35A
COP
3.182.59
Appearance dimension (W×L×Hmm)1,020×330×H1,350Heights including base 1,673
CompressorMaker (Model)ANB42FJJMT (MITSUBISHI ELECTRIC)
Type × Quantity
/ Operation method
Full sealing scroll x 1 unit / Inverter operation
Capacity control
100 ~ 40 - 0100 ~ 15 - 0
Rated outputkW2.5 x 1
RefrigerantTypeR410A
Filling amount
(Grid½)
kg4.3
Airside heat exchanger type
FIN & COIL TYPE
Waterside heat exchanger
TypePlate heat exchanger25A (1½B, screw style finish)
Inlet/outlet pipe
A25 / 25
BlowerType /
Output x quantity
kWPropeller fan / 0.074 × 2
Air volume (cooling/heating)
m³/min100
ControlDefrostingThe gas discharge reverse method

Water temperature controlExit temperature control

Driving control
Micom Controller (Fully Automatic driving)

Air conditioning, heating, outdoor air
/exit temperature (℃)
Temperature outside  : -25 ~35Temperature outside : -5 ~ 46
Cold and hot outlet temperature
 : 35 ~ 60
Cold and hot outlet temperature
 : 5 ~ 25

Protective deviceAn overcurrent relay, LPS/HPS, Exhaust gas temperature sensor,

Freeze prevention sensor, Water temperature control at the outlet,  Micom Controller. (Electronic exercise)


NoisedB531m from the Condenser unit fan
Product weight/driving weight
kg134 / 148


※ Standard application temperature: 

     Heating power: ambient temperature: 7℃, Hot water import port: 40℃, Hot water outlet: 45℃ 

※ Standard application temperature:

     Cooling ability: Outside temperature: 35℃, Coldwater outlet: 12℃, Coldwater outlet: 7℃

※ The specifications and specifications can be changed without prior notice due to product improvement.

※The above picture is a standard product image and may be partially changed depending on the design specifications and option conditions of the site. 

Main Use

Swimming pool
Swimming pool
Hot tub
Hot tub
Resort
Resort
Hotel
Hotel
Sports facility
Sports facility